GPM Series Steel Open Cooling Towers

GPM Series cross flow steel open cooling towers are generally of higher capacities, can work in series as a group for large projects. Enclosure made in special alloy coated steel or stainless steel. GPM towers are of optimized firm structure, high efficiency, low drift rate, and anti blocking. The towers dimensions can be customized to suit standard containers or particular project conditions. GPM towers are widely applied in different fields, to cool circulating water for Melting Furnaces, Induction Heaters, Metal Parts Production Lines, Hydraulic Stations, Power Generators, and other utilities requiring massive cooling water, but not highly demanding on water quality. Initial invest in open towers is lower, but water consumption rate is higher comparing to closed loop cooling towers.
Availability:
Quantity:

Configurations

 

 

STRUCTURE & CASING

STRUCTURE & CASING

The standard enclosure is made of the latest type of Highly Corrosion-resistant coated steel sheet with a coating composition of Zn+Al(11%)+Mg(3%), and a trace amount of silicon, originally imported from Nippon Steel or Posco. The panels are sheared and folded precisely in whole cold machining process, then densely bolted and sealed for water tightness, with sufficient reinforcing bars, preventing deforming during hoisting process in fields. Each tower is completed with maintenance access and doors of maximized size, for internal inspection convenience. 

 

 

 

 

NON-DIRECT DRIVE AXIAL FANS

NON-DIRECT DRIVE AXIAL FANS

A part of open loop series adopt non-direct drive axial fans, fitted with al-alloy airfoil blades perfectly balanced and coupled with gear box or belts with spead reducer, to a weather proof TEFC three-phases electric motor. The fan casing is a galvanized steel cylinder to draw the air vertically and avoid the risk of recirculation. The tip speed of the impeller is limited to keep the noise level within acceptable limits.  

 

 

 

 

 

WET DECK FILLWET DECK FILL

The fills are formed in flame-retardant PVC sheets with a special shape design of herringbone surface, to distribute water evenly over the entire fill area for maximal thermal performance, can be integrated with air inlet louvers and drift eliminators. For medium fouled water, fill types with enlarged grids are available to reduce the chances of blocks. All the raw materials are of virgin grade from approved suppliers, with long service life in tough environment.

 

 

DRIFT ELIMINATOR

DRIFT ELIMINATOR

Cellular Drift Eliminators are specifically designed to achieve maximum drift removal. With significantly lower pressure drop. The modules are constructed of a series of sinusoidal-shaped, corrugated PVC sheets that are mechanically assembled to mating sinusoidal structural waves, forming closed cells. These cells force the drift droplets being carried in the leaving airstream to make three distinct changes in direction. When the air is forced to change direction, the inertia of the water droplets keeps them moving in a straight line, causing them to impact the wall of the drift eliminator and drain back into the wet section of the tower.

 

 


 

AIR INLET LOUVERS

AIR INLELOUVERS

Cellular air Inlet louvers with advanced design improve air flow into the cooling tower, keep out debris, eliminate water splash-out, which otherwise can cause icing, near-site water damage,and unnecessary water loss. The deign restrict the amount of sunlight into the cooling tower to impede algae growth, reduce noise from the tower, and improve the tower's appearance.


 

       

SPRAY NOZZLES FOR OPEN TOWERS

 

SPRAY NOZZLES FOR OPEN TOWERS

The Spiral Target Nozzles used for GOM Series open towers, injection molded in polypropylene unit consisting of two parts, main body with integral target diffuser and a snap-on insert or orifice cap. The nozzles installed in bottom of the hot water distribution basins, to eliminate water diffusion decks below the hot water basins, provide full water coverage of the fills by gravity flow, removable and replaceable but of long service life. Sizes and variety depends on the tower size, water flow rate and water quality.

 

 

 

 

FLOAT VALVE

FLOAT VALVE

Heavy duty floating valve, made in stainless steel, floating ball in engineering plastic or stainless steel, with long service life. Water level ad justable.   

 

 


ANTI-EDDY FILTER

 

 

ANTI-EDDY FILTER

Effectively filting the sundries, with anti-eddy arrangement, preventing air bubbles sucked into the pumps, punched in the same material as the enclosure, highly corrossion resistant.

 


 

 

 

 

FASTENERS

 

FASTENERS

Fastners of leading brands, standard materials in steel dacromet treated, stainless steel on options. Intensity of fastners is higher than average.

 

 

 

 

 

 

Data Sheet

Model No. Nominal
Tons
Fan Power
  (kW)
Connecting Pipe(mm) Overall
Dimensions(mm)
Weight
Inlet Outlet Make   UP Overflow Drain L W H Net
(kg)
Operation     (kg)
GPM0109 S-1 136 3.7 DN150×2 DN150 DN25 DN50 DN50 1980 3910 3200 1800 3500
Q-1 156 5.5 DN150×2 DN150 DN25 DN50 DN50 1980 3910 3200 1800 3500
P-1 171 7.5 DN150×2 DN150 DN25 DN50 DN50 1980 3910 3200 1800 3500
GPM0115 Q-1 208 5.5 DN150×2 DN150 DN25 DN50 DN50 2550 4300 3220 2150 4600
P-1 231 7.5 DN150×2 DN150 DN25 DN50 DN50 2550 4300 3220 2150 4600
GPM0215 Q-1 264 5.5 DN200×2 DN200 DN25 DN50 DN50 2550 5530 3730 3350 7100
P-1 291 7.5 DN200×2 DN200 DN25 DN50 DN50 2550 5530 3730 3350 7100
O-1 322 11 DN200×2 DN200 DN25 DN50 DN50 2550 5530 3730 3350 7100
N-1 363 15 DN200×2 DN200 DN25 DN50 DN50 2550 5530 3730 3350 7100
M-1 383 18.5 DN200×2 DN200 DN25 DN50 DN50 2550 5530 3730 3350 7100
GPM0120 Q-1 312 5.5 DN200×2 DN200 DN40 DN65 DN50 3010 6070 3750 3850 8500
P-1 347 7.5 DN200×2 DN200 DN40 DN65 DN50 3010 6070 3750 3850 8500
O-1 395 11 DN200×2 DN200 DN40 DN65 DN50 3010 6070 3750 3850 8500
N-1 433 15 DN200×2 DN200 DN40 DN65 DN50 3010 6070 3750 3850 8500
M-1 460 18.5 DN200×2 DN250 DN40 DN65 DN50 3010 6070 3750 3850 8500
L-1 481 22 DN200×2 DN250 DN40 DN65 DN50 3010 6070 3750 3850 8500
GPM0126 P-1 393 7.5 DN200×2 DN200 DN40 DN65 DN50 3620 6400 3750 4850 11200
O-1 449 11 DN200×2 DN250 DN40 DN65 DN50 3620 6400 3750 4850 11200
N-1 490 15 DN200×2 DN250 DN40 DN65 DN50 3620 6400 3750 4850 11200
M-1 529 18.5 DN200×2 DN250 DN40 DN65 DN50 3620 6400 3750 4850 11200
L-1 560 22 DN200×2 DN250 DN40 DN65 DN50 3620 6400 3750 4850 11200
K-1 610 30 DN200×2 DN250 DN40 DN65 DN50 3620 6400 3750 4850 11200
GPM0132 O-1 513 11 DN250×2 DN250 DN40 DN65 DN50 4230 6830 3750 5750 13600
N-1 563 15 DN250×2 DN250 DN40 DN65 DN50 4230 6830 3750 5750 13600
M-1 605 18.5 DN250×2 DN250 DN40 DN65 DN50 4230 6830 3750 5750 13600
L-1 637 22 DN250×2 DN250 DN40 DN65 DN50 4230 6830 3750 5750 13600
K-1 700 30 DN250×2 DN300 DN40 DN65 DN50 4230 6830 3750 5750 13600
J-1 753 37 DN250×2 DN300 DN40 DN65 DN50 4230 6830 3750 5750 13600
GPM0226 O-1 555 11 DN250×2 DN250 DN50 DN65 DN65 3620 6830 4970 7250 15200
N-1 608 15 DN250×2 DN250 DN50 DN65 DN65 3620 6830 4970 7250 15200
M-1 654 18.5 DN250×2 DN250 DN50 DN65 DN65 3620 6830 4970 7250 15200
L-1 694 22 DN250×2 DN250 DN50 DN65 DN65 3620 6830 4970 7250 15200
K-1 757 30 DN250×2 DN300 DN50 DN65 DN65 3620 6830 4970 7250 15200
J-1 811 37 DN250×2 DN300 DN50 DN65 DN65 3620 6830 4970 7250 15200
GPM0326 N-1 658 15 DN250×2 DN250 DN50 DN65 DN65 3620 6830 5840 7950 16900
M-1 703 18.5 DN250×2 DN300 DN50 DN65 DN65 3620 6830 5840 7950 16900
L-1 741 22 DN250×2 DN300 DN50 DN65 DN65 3620 6830 5840 7950 16900
K-1 805 30 DN250×2 DN300 DN50 DN65 DN65 3620 6830 5840 7950 16900
J-1 857 37 DN250×2 DN300 DN50 DN65 DN65 3620 6830 5840 7950 16900
GPM0232 N-1 742 15 DN250×2 DN300 DN50 DN65 DN65 4230 6830 5840 8650 19400
M-1 791 18.5 DN250×2 DN300 DN50 DN65 DN65 4230 6830 5840 8650 19400
L-1 835 22 DN250×2 DN300 DN50 DN65 DN65 4230 6830 5840 8650 19400
K-1 907 30 DN250×2 DN300 DN50 DN65 DN65 4230 6830 5840 8650 19400
J-1 968 37 DN250×2 DN300 DN50 DN65 DN65 4230 6830 5840 8650 19400
I-1 1017 45 DN250×2 DN350 DN50 DN65 DN65 4230 6830 5840 8650 19400

NOTE

Nominal Tons are based upon temp.drop 35~29.5°C/ 95~85°F, WBT 25.5°C/ 78°F, and 0.681 m3/hr/ton.

 

 

GOM General Outline

 

Working Thoery

GOM Working Theory

WORKING THEORY

In GPM open cooling towers, the hot water is inlet to the water distribution basin on the top of the tower firstly, and spread onto the extensive surface of the wet deck fills after flowing through the spreading holes by gravity. Meanwhile the dry cool air is inlet through the side louvers of the tower, passing the fills across the water falls. During this process, a part of water is evaporated, with heat removed. The wet hot air is induced draught out of the tower into the atmosphere by the fans on the top, while the cooled water is collected back to the bottom collection basin with the eliminator, flowing back to the equipment requiring cooling water.

 

Features

PRODUCTS ADVANTAGES

 

 

 Capable and flexible in customized solutions

 Factory assembled for maximal installation convenience

 Modular design suits a wide range of heat rejection duties

 Compact design with minimal footprints

 Multiple corrosion resistant options

 Low sound operation options available

 More optimizing options available

 Performance and quality guaranteed